Bus Combined Smoke and Heat Detector with Built-in Siren

SKU: JA-111ST-A

Jablotron

  • Bus combined smoke and heat detector for detecting fire risk in residential and commercial interiors.
  • When powered from the control panel bus, it works as a system device (EN 54-7, EN 54-5).
  • With 3 x AA batteries inserted, it continues working as an autonomous unit if the 12 V supply or communication with the panel is lost (EN 14604).
  • Built-in siren reporting its own fire alarm, a fire alarm from another detector in the system and other alarm types (e.g. intruder alarm), with configurable sections.
  • Also indicates a dangerous situation optically with an integrated light.
  • Two separate sensors: an optical smoke detector (diffused light principle) and a class A1 heat detector that responds better to fires developing heat quickly with little smoke.
  • Not designed for industrial environments; must be installed by a Jablotron-certified technician.

Share:
General Features
Weight: 150 g
Power Supply: Bus 12 V DC (9–15 V); battery backup: 3 x alkaline LR6 (AA) 1.5 V / 2.4 Ah or 3 x lithium FR6 (AA) 1.5 V / 3 Ah. Note: Batteries not included
Battery Life: approx. 3 years
Operating Temperature: -10 °C to +70 °C
Certificate: EN 14604, EN 54-7, EN 54-5, EN 50130-4, EN 55022
Compatibility: JABLOTRON 100+ control panels (bus)
Dimension: Ø126 mm, height 52 mm
Mounting: 2 x ø3.5 x 40 mm screws (countersunk head)
Supported Features: Optical (light scattering) smoke detection, sensitivity m = 0.11–0.13 dB/m; class A1 heat detection (EN 54-5), alarm temperature +60 °C to +65 °C; built-in siren
Low battery voltage: 3.5 V
Rated current consumption: Standby: 5 mA; for cable selection: 150 mA

JA-111ST-A

PDF