SILVER 8 Zone Conventional Fire Alarm Panel

SKU: SILVER08

Cofem

The Cofem SILVER08 is an 8-zone conventional fire detection and fire alarm control panel. The key feature of the SILVER series is that zones and relay outputs are independent: with optional relay cards, up to 16 configurable relay outputs can be added to the panel. Up to 32 conventional detectors and call points can be connected to each zone. The LCD display and menu keys make operation simple, and the panel can also be connected to the loop of the Cofem LYON addressable system as a further element. Certified according to EN 54-2/A1 and EN 54-4/A1.

  • 8 detection zones, up to 32 devices per zone; zones and relay outputs are independent
  • 4, 8, 12 or 16 relay outputs with optional relay cards (dry contact SVL4/SVL8 or supervised SVS4/SVS8)
  • 2 independent supervised general sounder outputs (S1/S2) with 0–10 min delay
  • 1 immediate alarm dry contact output and 1 fault output with 0–10 min delay
  • 2 fused 30 V DC auxiliary outputs (30V and resettable 30VR)
  • LCD display and menu keys; Spanish and English languages included by default
  • Connects to the LYON addressable loop as an element; Modbus, CRI, I-Link and Remote versions available
  • Metal box with front-bolted door, 13 pre-drilled 28 mm entries, space for 2 × 12 V 7 Ah batteries, IP30
  • Certified to EN 54-2/A1 and EN 54-4/A1

Suitable for conventional projects that require many zones and relay control (door holders, ventilation, lifts, extinguishing release, etc.) such as factories, schools, hotels, shopping centre floors and public buildings. 2, 4, 12 and 16 zone models are also available in the series.

Share:
General Features
Current: Max. 2 A (in alarm); 2 mA per zone
Weight without batteries: 5 kg
Aux Output: 2 × 30 V DC 0.5 A (30V and resettable 30VR), fused
Battery: 2 × 12 V 7 Ah (batteries not included); charger 500 mA 27 V DC
Operating Temperature: -10 °C to +50 °C
Certificate: EN 54-2/A1, EN 54-4/A1
Communication: LYON addressable loop connection; Modbus, CRI, I-Link and Remote versions
Language: Spanish, English (default)
Dimension: 328 × 423 × 159 mm (with cover)
Input Voltage: 110–230 V AC
IP Koruma Standardı: IP30
Material: Metal box, front-bolted door, 13 pre-drilled 28 mm entries
Nominal Voltage: Zone voltage 19–22.6 V DC
Relay Output: 1 alarm (dry contact, immediate) + 1 fault (dry contact, 0–10 min delay); up to 16 configurable relays with optional cards
Siren Audio Output: 2 independent supervised sounder outputs (S1/S2), 30 V DC 0.5 A, 0–10 min delay
Zone: 8 zones (conventional); zones and relay outputs independent
Maximum number of devices: 32 devices per zone (detectors + call points)

SILVER08

PDF