IRON 4 Zone Conventional Fire Alarm Panel
SKU: IRON04
The Cofem IRON04 is a 4-zone conventional fire detection and fire alarm control panel designed for small and medium-sized installations. Up to 32 conventional detectors and manual call points can be connected to each zone. Its compact metal enclosure, test mode and configurable thresholds allow quick commissioning and compatibility with different detector types. Certified according to EN 54-2 and EN 54-4.
- 4 detection zones, up to 32 devices (detectors and call points) per zone
- 2 supervised general sounder outputs, delayable 0–7 min, protected by self-resetting fuses
- 1 immediate alarm output and 1 immediate fault output (NO/NC dry contacts)
- 1 supervised 30 V DC auxiliary output for fire door electromagnets, sirens, etc.
- Test Mode for quick testing of detectors and call points
- Configurable open line, detector alarm and call point alarm thresholds
- Metal box with screwed front door, 10 pre-drilled 28 mm cable entries, space for 2 × 2 Ah batteries
- Certified to EN 54-2 and EN 54-4, CE marked
An economical and reliable solution for shops, small businesses, warehouses, workshops and residential common areas requiring a small number of zones. Works with Cofem PUC-AR call points, A30X / A35B series conventional detectors and SIR24 series sounders. A 2-zone version (IRON02) is also available.
| General Features | |
|---|---|
| Weight without batteries: | 2.2 kg |
| Aux Output: | 1 × 30 V DC 0.5 A supervised auxiliary output (self-resetting fuse) |
| Battery: | 2 × 12 V 2 Ah SLA (batteries not included); charger 350 mA 27 V DC |
| Operating Temperature: | -10 °C to +50 °C |
| Certificate: | EN 54-2, EN 54-4, CE |
| Out Voltage: | 21 V nominal; S1/S2 sounder outputs 30 V DC 0.5 A |
| Power Consumption: | Max. 65 VA at 230 V AC; 2 mA standby per zone |
| Dimension: | 248 × 240 × 115 mm |
| Input Voltage: | 110/230 V AC, 50/60 Hz |
| IP Koruma Standardı: | IP30 |
| Material: | Metal box, screwed front door, 10 pre-drilled 28 mm entries |
| Relay Output: | 1 alarm + 1 fault dry contact (NO/NC), immediate activation |
| Siren Audio Output: | 2 supervised general sounder outputs, 0–7 min delay, self-resetting fuses |
| Zone: | 4 zones (conventional) |
| Maximum number of devices: | 32 devices per zone (detectors + call points) |